EVALUASI PENGARUH PENUTUPAN KATUP LCV TERHADAP KENAIKAN GAYA PADA IMPELLER POMPA SIRKULASI AIR HWP PLTP DARAJAT II

Evaluation of LCV Valve Closing Effect on Force Increase of HWP Circulating Water Pump Impeller in Darajat II Geothermal Power Plant
Undergraduate Theses from JBPTITBPP / 2008-07-04 17:11:08
Oleh : NUR KUNCORO HADI (NIM 13103050), S1 - Department of Mechanical Engineering
Dibuat : 2008, dengan 8 file

Keyword : valve closing, force increase, water pump impeller

Pembangkit Listrik Tenaga Panasbumi (PLTP) Darajat Unit II milik Chevron Geothermal Indonesia memiliki sistem sirkulasi air dari kondensor menuju cooling tower kemudian kembali lagi ke kondensor. Untuk mengatur debit aliran dari kondensor menuju cooling tower, digunakan katup butterfly yang diberi nama LCV. Sistem pengendalian LCV adalah tipe diskrit dengan dead band 1%. Adanya dead band mengakibatkan pergerakan LCV tidak halus, sehingga mengakibatkan perubahan kondisi aliran secara tiba-tiba. Masalah ini diperburuk dengan adanya overshoot tiap kali LCV menutup. Perubahan kondisi aliran diduga mengakibatkan pembebanan pada Hot Well Pump (HWP), sehingga menjadi penyebab kerusakan pompa. Pada penelitian tugas sarjana ini dilakukan evaluasi pengaruh penutupan katup terhadap HWP dan pencarian alternatif yang sesuai. Evaluasi dilakukan dengan cara melakukan pemodelan aliran pada sistem katup menggunakan perangkat lunak FLUENT. Setelah diketahui perubahan kondisi aliran akibat penutupan LCV, penelitian dilanjutkan dengan memodelkan aliran pada HWP menggunakan FLUENT. Hasil dari pemodelan aliran pada sistem katup adalah perubahan kondisi aliran. Kondisi aliran yang menjadi perhatian utama adalah perubahan laju aliran akibat penutupan katup. Hasil pemodelan aliran pada HWP adalah perubahan gaya yang terjadi pada impellernya akibat perubahan laju aliran massa. Hasil pemodelan kemudian dibandingkan dengan pemodelan sistem terdahulu dan sistem yang dikembangkan, sehingga didapatkan sistem aktuasi katup yang lebih baik.
Deskripsi Alternatif :

Darajat Unit II Geothermal Power Plant owned by Chevron Geothermal Indonesia has a circulating water system which circulate condensate from condenser to cooling tower and back to condenser. Inside this system, there is a butterfly valve called LCV that used to control the water flow from condenser to cooling tower. LCV position is controlled by a discrete type control system, having dead band of 1%. The dead band caused unsmooth movement of LCV, causing sudden flow condition changing. This problem has gotten worse by the overshoot acknowledged on every LCV closing. The sudden flow condition changing is believed to cause extra loading on Hot Well Pump (HWP) which may resulted in HWP breakdown. This final year project evaluates the effect of LCV closing on HWP and then finds the suitable solution. The evaluation is done by modeling the flow in the system using FLUENT software. Having knowledge of the flow condition changing caused by valve closing, the research continued by modeling the flow inside HWP, also using FLUENT. The result of system flow modeling is flow condition changing. Mass flow rate changing become the most concerned point. Then, by conducting HWP flow modeling using FLUENT, the knowledge of force changing because of mass flow rate changing on the HWP impeller is achieved. The result of present system modeling then compared to the result of previous system and developed system, giving the better system to be implemented.

Copyrights : Copyright Â(c) 2001 by ITB Central Library. Verbatim copying and distribution of this entire article is permitted by author in any medium, provided this notice is preserved.

One Response to “EVALUASI PENGARUH PENUTUPAN KATUP LCV TERHADAP KENAIKAN GAYA PADA IMPELLER POMPA SIRKULASI AIR HWP PLTP DARAJAT II”

  1. [...] [...]

Leave a Reply